Medium Voltage ABC Cable Construction
Phase Conductor | Circular compacted stranded H68 aluminium to BS2627. |
---|---|
Conductor Screen | Extruded semi-conductive layer. |
Insulation | XLPE. |
Insulation Screen | Extruded semi-conductive layer. |
Outer Sheath | HDPE. |
Support Conductor | Aluminium alloy conductor (AAAC/1120). |
Assembly | Three XLPE insulated cores are bundled around the AAAC/1120 support conductor in a right hand lay. |
Application:
Used for primary and secondary overhead distribution where limited space is available or desirable for rights of way.
Installed as an uninsulated conductor; however, covering is effective in preventing direct shorts and instantaneous flashovers should tree limbs or other objects contact conductors in such close proximity.
The resulting close-proximity configuration minimizes the amount of space and hardware required for line installation; particularly useful in congested areas such as alleyways or tight corridors.
Single Core Medium Voltage ABC Cable Parameter
Cross section | No. of wires | Conductor diam. | Overall Diameter | Minimum breaking load | Approx. weight | Max. DC-resistance at 20°C | Ampacity 90°C |
[mm²] | [mm] | [mm] | [kgf] | [kg/km] | [Ohm/km] | [A] | |
35 | 7 | 7.1 | 13.6 | 464 | 190 | 0.868 | 187 |
50 | 7 | 8.2 | 14.7 | 663 | 235 | 0.641 | 225 |
70 | 19 | 9.7 | 16.2 | 928 | 315 | 0.443 | 282 |
95 | 19 | 11.5 | 18 | 1259 | 400 | 0.32 | 345 |
120 | 19 | 12.9 | 19.4 | 1591 | 500 | 0.253 | 401 |
150 | 19 | 14.2 | 20.7 | 1988 | 580 | 0.206 | 456 |
185 | 37 | 16.2 | 22.6 | 2452 | 695 | 0.164 | 525 |
240 | 37 | 18.4 | 24.9 | 3182 | 875 | 0.125 | 625 |