Application: instrument cable suitable for fixed installations in damp locations and open spaces. The electrostatic screen protects against outer interference fields
Standards: BS 7917; IEC 60331-31 Fire resistant; IEC 60332-3A Flame retardant; IEC 60754-1; IEC 60754-2 Corrosivity IEC 61034-2 Smoke density Cold bend and impact (-40°C) (on request) CSA C22.2 No. 38-95 (on request).
Individual Screen Instrument Cable
Product Feature
Conductor: Plain annealed circular stranded copper conductor, conform to BS 6360 class 2.
Insulation: PE( polyethylene)/PVC.
Pairing: Two insulated cores shall be uniformly twisted together to form a pair with maximum bay length of 100mm.
Cabling: twisted pairs are laid up to together, if necessary filled with non-hygroscopic material Compatible with the insulation.
Overall screening: accumulated pars screen with aluminum/mylar tape. helically applied with tghe metallic side down, in electrical connect with tinned annealed copper drain wire of 0.5mm2
Sheath: PVC
Individual+Overall Screen Instrument Cable
Conductor: plain annealed circular stranded copper conductor, conform to BS 6360 class 2.
Insulation:PE(polyethylene)
Pairing: two insulated cores shall be uniformly twisted together to form a pair with maximum lay length of 100mm.
Pair identification: Color code as per appendix A.
Individual screening: each pair screened with aluminum/maylar tape,hlically applied with the metallic side down, in electrical contact with a tinned annealed copper drain wire of 0.5mm2
Cabling: twisted pairs are laid up together, if necessary filled with nonhygroscopic material compatible with the insulation.
Overall screening: Accumulated pairs screened with aluminum/mytar tape, helically applied with the metallic side down in electrial contact with a tinned annealed copper drain wire 0.5mm2
Sheath: PVC(polyvinyl chioride)
Armoured Overall Screen Instrument Cable
Conductor: plain annealed circular stranded copper conductor, conform to BS 6360 class 2.
Insulation: PE(polyethylene)
Pairing: two insulated cores shall be uniformly twisted together to form a pair with maximum lay length of 100mm.
Pair identification: Color code as per appendix A.
Cabling: twisted pairs are laid up togeter, if necessary filled with non-hygroscopic material compatible with the insulation.
Overall screening: Accumulated pairs screened with aluminum/mytar tape, helically applied with the metallic side down in electrical contact with a tinned annealed copper drain wire 0.5mm2
Bedding: PE, color black
Armoring: Galvanized steel round wire over the bedding.
Sheath: PVC(polyvinyl chioride)
Armoured Individual+Overall Screen Instrument Cable
Conductor: plain annealed circular stranded copper conductor, conform to IEC 60228 or BS 6360 class 2.
Insulation: PE (polyethylene)
Pairing: two insulated cores shall be uniformly twisted together to form a pair with maximum lay length of 100mm.
Pair identification: Color code as per appendix A.
Overall screening: each pairs screened with aluminum/mytar tape, helically applied with the metallic side down in electrical contact with a tinned annealed copper drain wire 0.5mm2
Cabling: twisted pairs are laid up together, if necessary filled with non-hygroscopic material compatible with the insulation.
Overall screening: Accumulated pairs screened with aluminum/mytar tape, helically applied with the metallic side down in electrical contact with a tinned annealed copper drain wire 0.5mm2
Armoring: Galvanized steel round wire over the bedding.
Sheath: PVC(polyvinyl chioride)