H07V-U cable : is intended for the installation to the inside of apparatus as well as for the protective laying to the lightings, in dry rooms, in production facilities, switch and distributor boards, in tubes, under and surface mounting of plasters.
H07V-K cable: is used for the internal wiring of electric motors and transformers as well as other electrical appliances and lighting applications. It can be used in and at electronic appliances for measuring, regulating and controlling. The cables are also ideal for laying in pipes, surface wiring and conduit installations. Specifications according to HD 516 apply for respective specific applications.
H07V-R cable : is preferably for installation indoors, in cable ducts and in industrial plants or switching stations, under ground installation. Can be used in switchboards and distributor boards or where a thicker strand of multi-wire is required
Voltage: 450/750V
Conductor:
1. H07V-U: Solid Copper,
2. H07V-K: Stranded copper class 5 according to DIN VDE 295
3. H07V-R: Stranded Copper Conductor
Insulation: PVC
Standards: DIN,
Technical Data: Max. operating temperature 70 ºC, Short circuit temperature 160 ºC.
H07V-U Technical characteristics:
Nominal cross-sectional area | Approx. Dia. of cable | Weight | DC resistance at 20°C | Max. current Carrying capacity at 30°C |
|
(mm2) | (mm) | (Kg/km) | (Ω/km) | Pipe A | Air A |
1.5 | 2.75 | 19.17 | 12.1 | 16 | 24 |
2.5 | 3.33 | 29.99 | 7.41 | 20 | 32 |
4 | 3.79 | 44.23 | 4.61 | 26 | 42 |
6 | 4.28 | 62.66 | 3.08 | 35 | 55 |
10 | 5.50 | 105.7 | 1.83 | 46 | 75 |
H07V-K Technical characteristics:
Dimensions – conductor cross-section | Construction of individual conductor | Insulation thickness | Conductor resistance at 20 °C | Cu weight | Cable weight |
section (mm²) | n x mm | mm | Ω/km | kg/km | kg/km |
1,5 | 30 x 0,25 | 0,7 | 13,3 | 14,4 | 20 |
2,5 | 50 x 0,25 | 0,8 | 7,98 | 24,0 | 32 |
4 | 56 x 0,30 | 0,8 | 4,95 | 38,4 | 46 |
6 | 84 x 0,30 | 0,8 | 3,30 | 57,6 | 65 |
10 | 80 x 0,40 | 1,0 | 1,91 | 96,0 | 115 |
16 | 128 x 0,40 | 1,0 | 1,21 | 153,6 | 170 |
25 | 200 x 0,40 | 1,2 | 0,780 | 240 | 260 |
35 | 280 x 0,40 | 1,2 | 0,554 | 336 | 360 |
50 | 400 x 0,40 | 1,4 | 0,386 | 480 | 515 |
70 | 356 x 0,50 | 1,4 | 0,272 | 672 | 710 |
H07V-R Technical characteristics:
Nominal cross- | App. | Weight | Conductor DC | Max. current carrying | |
sectional area | Dia. of cable | Cable | resistance at 20°C | capacity at 30°C | |
(mm2) | (mm) | (Kg/km) | (Ω/km) | Pipe A | Air A |
1.5 | 2.93 | 19.85 | 12.1 | 16 | 25 |
2.5 | 3.58 | 31.49 | 7.41 | 20 | 34 |
4 | 4.09 | 45.83 | 4.61 | 26 | 45 |
6 | 4.66 | 65.23 | 3.08 | 35 | 57 |
10 | 5.96 | 108.29 | 1.83 | 46 | 75 |
16 | 7.04 | 166.46 | 1.15 | 62 | 100 |
25 | 9 | 280.97 | 0.727 | 82 | 130 |
35 | 10.05 | 368.7 | 0.524 | 100 | 160 |
50 | 11.8 | 509.69 | 0.387 | 120 | 200 |