Professional interlocked armore cable manufacturer, Meet your kinds of requirement of AC90, ACWU90, Teck 90 Control Cable, Teck 90 EPR/XPLE Cable, Aluminum Alloy Interlocked Armor(AIA) Cable. With over 30 years production experience and 15 years export experience, factory price without any third party.
The cable size can be customized according to your requirement, On-time delivery.
Teck 90 Power Cable 1kV-T90 (16-09)
- Conductor: Class B stranded copper
- Size(AWG/MCM): 1,2,4,6,8,1/0,2/0,4/0AWG Or 250, 300,350,500,750 MCM
- Insulation: Cross-Linked Polyethylene (XLPE)
- Grounding Conductors: Uninsulated Class B stranded grounding conductor
- Assembly: Multiple conductor cables assembled with suitable fi llers and binder tape
- Colour Code:
– 2/C black, white
– 3/C red, black, blue
– 4/C red, black, blue, white
– For cables larger than No. 2 AWG or more than 4/C, the insulation is black and numbered - Inner Jacket: Polyvinyl Chloride (PVC) Armour; Aluminum Interlocked Armour (AIA)
- Overall Jacket : Black PVC (optional colours available)
Operating Temperatures
- -40°C – CSA Cold Bend and Impact Temperature
- -40°C – Min. Installation Temperature
- 90°C – Max. Continuous Operating Temperature
Teck 90 1/C Cu 1KV XLPE/PVC AIA PVC-NS
Conductor: Class B stranded copper
– compressed or compact
– in accordance with ASTM B3 and ASTM B8
Insulation:
- XLPE (Cross Linked Polyethylene)
- Minimum Average Thickness: 250 kcmil to 1000 kcmil – 0.090 inches (2.3 mm)
- 90°C rated
Concentric Bonding Conductors:
- Class B concentric bare copper wire serve
Inner Jacket:
1. Black PVC
2.Thickness – 250 kcmil to 1000 kcmil = 0.060″ (1.5 mm)- minimum average
Armour: Aluminum Interlocked Armour (AIA)
Overall Jacket:
- Black PVC (optional colours available)
- Minimum Thickness
– 250 kcmil to 400 kcmil = 0.050 inches (1.3 mm)
Operating Temperatures:
-40°C – CSA Cold Bend and Impact Temperature
Teck 90 5KV 1 Core Non shielded-TR-XLPE Cable
Conductor:
1. Class B stranded copper – compressed or compact
– in accordance with ASTM B3 and ASTM B8
2. Optional Class B compact stranded 8000 Series Aluminum ACM
Insulation
1.TR-XLPE (tree retardant cross linked polyethylene
2. Thickness: 0.090 inches (2.3 mm) – nomina
3. Insulation Level: 100% – ungrounded system
4. Temperature Rating: 90°C
Conductor Shield: Extruded semi-conducting thermosetting polymeric layer
Concentric Bonding Conductors
-Class B – concentric bare copper wire serve
Inner Jacket: Black PVC Jacket thickness:
1. 2 AWG to No. 1/0 AWG = 0.045”(1.2 mm)
2. 2/0 AWG to 1000 kcmil = 0.060”(1.6 mm)
Armour: -Aluminum Interlocked Armour (AIA)
-Optional Galvanized Steel Interlocked Armour (GSIA)
Overall Jacket
-Orange PVC (optional colours available)
-Thickness:
1. 2 AWG to 400 kcmil = 0.045”(1.2 mm)
2. 500 kcmil to 1000 kcmil = 0.055”(1.4 mm)
Operating Temperatures
1. -40°C – CSA Cold Bend and Impact Temperature
2. -25°C – Min. Installation Temperature
3. 90°C – Max. Continuous Operating Temperature
4. 140°C for Emergency Overload Temperature
5. 250°C for Short Circuit Temperature
Teck 90 5KV 3 Core Non-Shielded EPR/XLPE Cable
1. Class B stranded copper
– compressed or compact
– in accordance with ASTM B3 and ASTM B8
2. Optional Class B compact stranded 8000 Series Aluminum ACM
Conductor Shield
1. Extruded semi-conducting thermosetting polymeric layer
Grounding Conductor
1. Class B compressed or compact stranded bare copper
Insulation
1. No-Lead EPR (ethylene propylene rubber)
2. Thickness: 0.090” (2.3 mm) – nominal
3. 90°C rated
Inner Jacket
1. Black PVC
2. Thickness:
– No. 2 AWG to No. 3/0 AWG = 0.080” (2.0 mm)
– No. 4/0 AWG to 500 kcmil = 0.110” (2.8 mm)
– 750 kcmil to 1000 kcmil = 0.140” (3.6 mm)
Fillers
1. Non-wicking, non-hygroscopic
Armour
1. Aluminum Interlocked Armour (AIA)
2. Optional Galvanized Steel Interlocked Armour (GSIA)
Overall Jacket
1. Orange PVC (optional colours available
2. Thickness:
– No. 2 AWG to 250 kcmil = 0.060” (1.5 mm)
– 350 kcmil to 750 kcmil = 0.075” (1.9 mm)
– 1000 kcmil = 0.090” (2.3 mm)